PCB mounting D.C. Shunts are designed and manufactured to order, for UPS systems applications.
Overload Withstands 1.2 X RATED CURRENT CONTINUOUSLY
5 Second Withstands 10 X RATED CURRENT
Temperature Coefficients 0.002 % PER °C BETWEEN 25°C AND 80°C
Ambient Temperature CALIBRATED FOR 23°C THE WORKING RANGE IS -20°C TO +60°C
Temperature Rise CORRECTLY MOUNTED IN FREELY CIRCULATING AIR, THE TEMPERATURE RISE WILL NOT EXCEED 90°C AT THE CENTRE LINE OF THE ELEMENT, AND 60°C AT THE JOINT LINE, BASED ON THE AMBIENT OF 23°C